DocumentCode :
466366
Title :
Operating Results of the Albany (NY) High Temperature Superconducting Cable System
Author :
Weber, C. ; Lee, R. ; Masuda, T. ; Moscovic, J.
Author_Institution :
SuperPower Inc., Schenectady, NY
fYear :
2007
fDate :
24-28 June 2007
Firstpage :
1
Lastpage :
4
Abstract :
The Albany HTS Cable Project team (BOC, National Grid, Sumitomo Electric, Superpower) have built and tested a 350-m long HTS cable and cryogenic system rated at 48 MVA (800rms, 34.5-kV). The cable system included the world´s first demonstration of an HTS cable-to-cable joint (or splice) as well as some novel design aspects in both the cryogenic refrigeration system and the terminations. The cable was installed and began operation in July 2006. This paper will summarize the testing and operational aspects of the HTS cable system and its integration into the existing National Grid 34.5-kV network.
Keywords :
cryogenics; power grids; refrigeration; superconducting cables; Albany HTS Cable Project team; Albany high temperature superconducting cable system; HTS cable-to-cable joint; National Grid; apparent power 48 MVA; cryogenic refrigeration system; voltage 34.5 kV; Bismuth compounds; Cryogenics; High temperature superconductors; Power cables; Refrigeration; Superconducting cables; Superconducting transmission lines; System testing; Underground power cables; Wire; Cryogenic Refrigeration Systems; HTS Cables; High Temperature Superconductors; Superconducting Cables;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2007. IEEE
Conference_Location :
Tampa, FL
ISSN :
1932-5517
Print_ISBN :
1-4244-1296-X
Electronic_ISBN :
1932-5517
Type :
conf
DOI :
10.1109/PES.2007.386219
Filename :
4275985
Link To Document :
بازگشت