Title :
The Influences of T-Joint Core Design on No-Load Losses in Transformers
Author :
Haidar, Ahmed M. A. ; Al-Dabbagh, M.
Author_Institution :
Univ. Malaysia Pahang, Kuantan, Malaysia
Volume :
32
Issue :
3
fYear :
2013
fDate :
May-June 2013
Firstpage :
40
Lastpage :
48
Abstract :
The main objective of this article is to compare the performance of transformers with respect to different core designs based on T-joint configurations of 23o, 45o, 60o, and 90o. The quantitative analysis of localized flux distribution and loss calculation is determined through the significant progress of numerical field calculations using the finite element method. The transformer core has been designed and simulated using QuickField software. From the results, it was found that the best core design is a 60o T-joint configuration in terms of the no-load losses and flux distribution.
Keywords :
finite element analysis; power engineering computing; power transformers; transformer cores; QuickField software; T-joint configurations; T-joint core design; finite element method; localized flux distribution; loss calculation; no-load losses; numerical field calculations; transformer core; transformer performance; Design methodology; Electromagnetic induction; Load management; Loss measurement; Transformers; Voltage control;
fLanguage :
English
Journal_Title :
Potentials, IEEE
Publisher :
ieee
ISSN :
0278-6648
Type :
jour
DOI :
10.1109/MPOT.2012.2211911