Title :
Effects of vapor with different chemical properties on corona partial discharges of stator windings
Author :
Chuanyang Li ; JianCheng Song ; Lingyan Lin ; Zhipeng Lei ; Wen Su ; Xiaoyu Bi
Author_Institution :
Shanxi Key Lab. of Coal Min. Equip. & Safety Control, Taiyuan Univ. of Technol., Taiyuan, China
Abstract :
The effects of vapor with different chemical properties on corona partial discharges (PDs) at the junction section of the semi-conductive tape and the stress grading tape of stator windings were investigated. The phase resolved partial discharge (PRPD) patterns were collected during the experiment to obtain the characteristics of the PDs. The result has confirmed that relative humidity (RH) of the vapor with different chemical properties can cause corona discharge to change significantly. The acidic vapor can suppress corona discharge effectively. When RH exceeds 60%, the corona discharge would be hardly induced even though the voltage is boosted up to twice the operating voltage. When RH is over 80%, corona discharge will develop into phenomenon of creeping on the surface of the ground wall insulation and can hardly be collected through the capacitive coupler.
Keywords :
corona; electric connectors; partial discharges; stators; capacitive coupler; chemical properties; corona discharge suppression; corona partial discharges; ground wall insulation; junction section; phase resolved partial discharge patterns; relative humidity; semi-conductive tape; stator windings; stress grading tape; vapor effects; Chemicals; Coils; Corona; Discharges (electric); Insulation; Partial discharges; Stator windings; Corona; humidity; online monitoring; partial discharges; stator windings;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2014.6832238