    Long front time switching impulse tests of long air gap in UHV projects at altitude of 2100 m

  • Author

    Yongli Liao ; Chao Gao ; Ruihai Li ; Guoli Wang ; Guoqing Lu

  • Author_Institution
    Electr. Power Res. Inst., China Southern Power Grid Co., Ltd., Guangzhou, China
  • Volume
    21
  • Issue
    3
  • fYear
    2014
  • fDate
    Jun-14
  • Firstpage
    982
  • Lastpage
    987
  • Abstract
    The past and recent investigations show that front time of switching overvoltage waveforms in Ultra High Voltage (UHV) system of long distance transmission are mostly in long wave front time exceeding 1000 μs. The long front time of switching impulse voltage has been deviated from the critical front time. This paper is involved with breakdown characteristics and external insulation design under long front switching impulse voltage in UHV system. All the Tests were performed on an outdoor UHV test site at altitude of 2100 m, China Southern Power Grid Co. Ltd. (CSG). Breakdown characteristics of rod-plane and actual size tower-conductor in ±800 kV UHV DC transmission line are obtained under wide front time switching impulse voltages from 100 to 2350 μs. From the comprehensive studies of such tests, it is proposed that U50 of front time exceeding 1000 μs increases 20% compared with the results of standard switching impulse (250/2500 μs) tests and standard deviations of U50 is 6% in UHV transmission system. Finally, an air gap insulation design procedure in conductor-tower of UHV transmission line at altitude of 0-2000 m is presented. Long front time switching impulse strength of conductor-tower gap is proposed into selection by reference in UHV transmission line insulation design.
  • Keywords
    HVDC power transmission; air gaps; insulation testing; poles and towers; China Southern Power Grid Co. Ltd; DC transmission line; UHV projects; UHV system; UHV transmission line insulation design; altitude 0 m to 2000 m; altitude 2100 m; long distance transmission; overvoltage waveforms; time 100 mus to 2350 mus; ultra high voltage system; voltage 800 kV; Equations; Insulation; Mathematical model; Power transmission lines; Standards; Switches; Voltage control; Ultra-high-voltage insulation; air gaps; long wave front time; switching surge; switchingimpulse voltage test;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.6832240
  • Filename
    6832240