• DocumentCode
    473194
  • Title

    The Scheme of Single-Phase Adaptive Reclosing on EHV/UHV Transmission Lines

  • Author

    Li Bin ; Zhang Shuo ; Crossley, Peter ; Bo Zhiqian

  • Author_Institution
    Key Lab. of Power Syst. Simulation & Control of Minist. of Educ., Tianjin Univ., Tianjin
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    116
  • Lastpage
    120
  • Abstract
    Automatic reclosure (AR) is extremely effective in improving the reliability, stability and security of the overall power system. However, the present autoreclosure operates blindly and practices employing a fixed time. In the case of permanent fault, a second shock to the system can cause irreparable damage to expensive equipments. According to characters of transient faults and permanent faults, this paper introduces the method of Bergeron line model into the field of single-phase adaptive reclosing (SPAR). Therefore, the paper proposes a novel scheme based on the calculation of Bergeron model to realize SPAR. Theoretical analysis and simulation prove that the proposed scheme of single-phase adaptive reclosing is valid with high sensitivity and reliability.
  • Keywords
    fault location; power transmission faults; power transmission lines; power transmission protection; Bergeron line model; EHV transmission lines; UHV transmission lines; automatic reclosure; permanent faults; single-phase adaptive reclosing; transient faults; Adaptation model; Circuit faults; Fault currents; Harmonic analysis; Power system transients; Power transmission lines; Transient analysis;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4496970