Title :
A Novel Adaptive Reclosure Criterion For EHV Transmission Line
Author :
Xiangning Lin ; Bing Wang ; Xiangli Deng ; Bo, Z.Q. ; Klimek, A.
Author_Institution :
Three Gorge Univ., Yichang
Abstract :
Autoreclosure schemes have been widely used in power system and an effective way to improve greatly the dependability and stability of power systems. However, most of these schemes adopt a presetting time to reclose breaker after a tripping operation. There are many problems due to the conventional reclosure schemes. In this paper, a self-adaptive auto-reclosure criterion using dual-window transient energy ratio (ER) for transmission line is proposed. A novel concept of close-opening - open-closing morphological gradient (COOCG) is put forward. COOCG has lower unbalanced output when processing the steady-state signal, and a better performance in extracting of high-frequency(HF) energy of the voltages, therefore, the threshold of ER can be lowered to improve the successful rate of fault discrimination. Many simulation results for the models established with EMTP show that COOCG is promising to be used in the real power systems.
Keywords :
EMTP; fault diagnosis; power transmission faults; power transmission lines; transient analysis; EHV transmission line; EMTP; close-opening-open-closing morphological gradient; dual-window transient energy ratio; fault discrimination; high frequency energy; power system stability; real power systems; self-adaptive autoreclosure criterion; steady-state signal; Band pass filters; Circuit faults; Integrated circuit modeling; Noise; Power system stability; Power system transients; Transient analysis;
Conference_Titel :
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location :
Glasgow
Print_ISBN :
978-0-86341-902-7