• DocumentCode
    473232
  • Title

    Accurate Location of Faults on Series-Compensated Lines with Use of Two-End Unsyncuronised Measurements

  • Author

    Saha, M.M. ; Izykowski, J. ; Rosolowski, E. ; Balcerek, P. ; Fulczyk, Marek

  • Author_Institution
    ABB AB, Stockholm
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    338
  • Lastpage
    343
  • Abstract
    This paper presents accurate fault location algorithm for series compensated lines. Use of two-end current and voltage signals with a more general case of unsynchronised measurements is considered. Two ways of synchronisation of measurements are presented. The subroutines of the developed algorithm are formulated with use of the generalised fault loop model, leading to compact formulae. High accuracy of fault location is assured due to strict considering the distributed parameter line model. The distance to fault calculation is independent on the parameters of the compensating bank. Multi-criteria efficient procedure for selecting the valid subroutine is presented. The developed fault location algorithm has been thoroughly tested using signals taken from ATP-EMTP versatile simulations of faults on a series-compensated transmission line. The example of fault location is presented and discussed.
  • Keywords
    EMTP; power system faults; power transmission lines; ATP-EMTP; Electromagnetic Transients Program; distributed parameter line model; fault calculation; fault location algorithm; fault loop model; series compensated lines; series-compensated transmission line; two-end unsynchronised measurements; Algorithms; Current measurement; Equations; Fault location; Mathematical model; Synchronization; Voltage measurement;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4497008