    A Method for Controlled Fault Interruption Based on Predicted Current Behavior

  • Author

    Thomas, Robert ; Solver, C.E.

  • Author_Institution
    HV Products, ABB AB, Ludvika
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    708
  • Lastpage
    713
  • Abstract
    A method for prediction of the behaviour of fault currents has been developed for the application of controlled fault interruption (CFI). A generic, asymmetrical fault current model is used for predicting viable interruption current zero times, to which the trip commands of a circuit breaker can be synchronized in order to interrupt with pre-selected (optimum) arcing times in each phase. Analysis-of-variance (ANOVA) testing of the model against sampled current values is used to regulate control of the algorithm. The algorithm has been tested in simulations with a wide range of fault current cases and found to predict target current zero times within plusmn0.5 ms, even in presence of large random signal distortion.
  • Keywords
    circuit breakers; fault currents; fault diagnosis; ANOVA; analysis-of-variance; asymmetrical fault current model; circuit breaker; controlled fault interruption; current behavior prediction; preselected arcing times; random signal distortion; Circuit breakers; Circuit faults; Estimation; Fault currents; Integrated circuit modeling; Least squares approximations; Synchronization;