Elucidation of formation mechanism of by-products of copper sulfide deposition on insulating paper in oil-immersed transformer
Author :
Mizuno, Koji ; Nishiura, R. ; Kato, Fumiki ; Hikita, Masayuki
Author_Institution :
Adv. Technol. R&D Center, Mitsubishi Electr. Corp., Amagasaki, Japan
Volume :
21
Issue :
3
fYear :
2014
fDate :
Jun-14
Firstpage :
1376
Lastpage :
1383
Abstract :
Copper sulfide deposition on cellulosic insulating materials in oil-immersed transformers is evaluated by heating tests stipulated by IEC 62535. Although this method is suitable for evaluation of the corrosivity of unused insulating oil, the subject remains in diagnosis of the insulating oil used. It is because dibenzyl disulfide (DBDS), which is the prime compounds that cause copper sulfide deposition, is consumed by the reaction with copper during operating of transformer. Therefore, it is necessary to detect the existence of DBDS in insulating oil diagnosed as non-corrosivity by IEC 62535. The proceeding paper [6] reports that Bibenzyl (BiBz) and Dibenzyl sulfide (DBS) will be formed in the insulating oil as by-products of copper sulfide formation between copper and DBDS in oxygen-poor atmosphere which imitated the closed-type transformers. These by-products are considered to be the indication of copper sulfide formation. However, the influence of oxygen and addition agent (e.g. 2,6-di-tert-butylp- cresol) on the mechanism of the by-product formation is unclear. The purpose of this study is to elucidate the influence of oxygen and DBPC in by-products formation for development of diagnosis. It became apparent that benzyl alcohol, benzaldehyde and benzoic acid generate as by-products of copper sulfide formation in the air atmosphere which imitated the open-breathing transformers. Furthermore, it became apparent that the reaction product of benzyl radical and the radical of DBPC generates as by-product of copper sulfide formation in the insulating oil containing DBPC. These by-products are detectable even if DBDS disappears. Therefore, it is thought that diagnosis of the open-breathing transformer is possible by detecting these by-products.
Keywords :
IEC standards; copper compounds; power transformer insulation; power transformer testing; transformer oil; BiBz; DBDS; DBPC; DBS; IEC 62535; addition agent; air atmosphere; benzaldehyde; benzoic acid; benzyl alcohol; benzyl radical; bibenzyl; by-product formation; cellulosic insulating materials; copper sulfide deposition; corrosivity; dibenzyl disulfide; heating tests; oil-immersed transformers; open-breathing transformers; oxygen-poor atmosphere; unused insulating oil; Atmosphere; Compounds; Copper; Heating; Nitrogen; Oil insulation; Satellite broadcasting; Copper; copper compounds; oil insulation; paper insulation; sulfur; sulfur compounds; transformers;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2014.6832286
Filename :
6832286
Link To Document :
بازگشت