DocumentCode :
47952
Title :
Optimal Integration of Phasor Measurement Units in Power Systems Considering Conventional Measurements
Author :
Azizi, Sadegh ; Gharehpetian, G.B. ; Dobakhshari, A. Salehi
Author_Institution :
Sch. of Electr. & Comput. Eng., Univ. of Tehran, Tehran, Iran
Volume :
4
Issue :
2
fYear :
2013
fDate :
Jun-13
Firstpage :
1113
Lastpage :
1121
Abstract :
This paper presents an integer linear programming (ILP) framework for the optimal placement of phasor measurement units (PMUs), in the presence of conventional measurements. Furthermore, by the proposed method, the power system remains completely observable during all possible single contingencies for lines and measurement devices. In doing so, the potential of circuit equations associated with both PMUs and conventional measurements as well as the network topology are fully utilized by a system of equations to reach the minimum possible numbers of required PMUs. The limitation of communication channels is also taken into account in the proposed ILP-based framework. The method is implemented on several IEEE test systems which have already been equipped with conventional measurements. The comparison between obtained results of the proposed method and those of other methods reveals its superiority in the modeling of robust PMU placement problem (OPP) in the presence of conventional measurements. As such, a smooth transition from the SCADA-based monitoring system to the PMU-dominated WAMS is ensured. Moreover, this method is successfully applied on three large-scale test systems, which demonstrates it can effectively be employed for robust OPP in realistic power systems.
Keywords :
integer programming; linear programming; phasor measurement; ILP-based framework; PMU optimal placement; PMU-dominated WAMS; SCADA-based monitoring system; integer linear programming framework; measurement devices; network topology; phasor measurement unit optimal integration; phasor measurement unit optimal placement; power systems; robust OPP; robust PMU placement problem; Current measurement; Equations; Mathematical model; Observability; Phasor measurement units; Power measurement; Power systems; Contingency; integer linear programming (ILP); observability; optimal PMU placement (OPP); phasor measurement unit (PMU);
fLanguage :
English
Journal_Title :
Smart Grid, IEEE Transactions on
Publisher :
ieee
ISSN :
1949-3053
Type :
jour
DOI :
10.1109/TSG.2012.2213279
Filename :
6313964
Link To Document :
بازگشت