• DocumentCode
    482261
  • Title

    Simulation for researching stator insulation structure of 135MW evaporative cooling turbo-generator by marinating

  • Author

    Ru, Luan ; Zhi-jian, Jiang ; Ying-zi, Li

  • Author_Institution
    Dept. of Electr. Eng., Beijing Inst. of Civil Eng. & Archit., Beijing
  • fYear
    2008
  • fDate
    17-20 Oct. 2008
  • Firstpage
    132
  • Lastpage
    135
  • Abstract
    In order to apply evaporative cooling technical to a high voltage and large capacity turbo-generator that will be used for a main power generator, the problem of designing reasonable insulation structure is needed to be solved. This paper offers immerging evaporative cooling stator, according to its specialties. This paper calculates and analysis the electric field and the temperature field in immerging evaporative cooling stator insulation structure in detail, then summarizes the distribution rules or specialties of these two fields. As results this paper gives the stator insulation thickness which is reduced greatly compared with traditional one and the current density , aiming to 135 MW evaporative cooling turbo-generator. The conclusion has been tested and is worthy of using for reference.
  • Keywords
    cooling; evaporation; machine insulation; stators; temperature distribution; turbogenerators; electric field distribution analysis; evaporative cooling turbo-generator; power 135 MW; power generator; stator insulation structure; temperature field distribution analysis; Computational modeling; Cooling; Dielectric liquids; Dielectrics and electrical insulation; Oil insulation; Power transformer insulation; Stator cores; Temperature distribution; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems, 2008. ICEMS 2008. International Conference on
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-3826-6
  • Electronic_ISBN
    978-7-5062-9221-4
  • Type

    conf

  • Filename
    4770665