DocumentCode
48852
Title
A Multilevel Medium-Voltage Inverter for Step-Up-Transformer-Less Grid Connection of Photovoltaic Power Plants
Author
Islam, Md Rafiqul ; Youguang Guo ; Jianguo Zhu
Author_Institution
Center for Electr. Machines & Power Electron., Univ. of Technol. Sydney, Sydney, NSW, Australia
Volume
4
Issue
3
fYear
2014
fDate
May-14
Firstpage
881
Lastpage
889
Abstract
Recently, medium (0.1-5 MW) and large (>5 MW) scale photovoltaic (PV) power plants have attracted great attention, where medium-voltage grid connection (typically 6-36 kV) is essential for efficient power transmission and distribution. A power frequency transformer operated at 50 or 60 Hz is generally used to step up the traditional inverter´s low output voltage (usually ≤400 V) to the medium-voltage level. Because of the heavy weight and large size of the power frequency transformer, the PV inverter system can be expensive and complex for installation and maintenance. As an alternative approach to achieve a compact and lightweight direct grid connection, this paper proposes a three-phase medium-voltage PV inverter system. The 11-kV and 33-kV PV inverter systems are designed. A scaled down three-phase 1.2-kV test rig has been constructed to validate the proposed PV inverter. The experimental results are analyzed and discussed, taking into account the switching schemes and filter circuits. The experimental results demonstrate the excellent feature of the proposed PV inverter system.
Keywords
distribution networks; photovoltaic power systems; power filters; power grids; power transformers; switching convertors; transmission networks; PV power plant; filter circuit; frequency 50 Hz; frequency 60 Hz; installation; lightweight direct grid connection; maintenance; medium-voltage grid connection; multilevel medium-voltage inverter; photovoltaic power plant; power 0.1 MW to 5 MW; power distribution; power frequency transformer; power transmission; step-up-transformer-less grid connection; switching scheme; three-phase medium-voltage PV inverter system; voltage 1.2 kV; voltage 6 kV to 36 kV; Insulated gate bipolar transistors; Inverters; Medium voltage; Photovoltaic systems; Topology; Grid integration; PV inverters; medium-voltage; photovoltaic (PV) power plants; step-up-transformer-less;
fLanguage
English
Journal_Title
Photovoltaics, IEEE Journal of
Publisher
ieee
ISSN
2156-3381
Type
jour
DOI
10.1109/JPHOTOV.2014.2310295
Filename