DocumentCode :
49431
Title :
Power flow in PME distribution systems during an open neutral condition
Author :
Halevidis, Constantinos D. ; Koufakis, Emmanuel I.
Author_Institution :
Sch. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Athens, Greece
Volume :
28
Issue :
2
fYear :
2013
fDate :
May-13
Firstpage :
1083
Lastpage :
1092
Abstract :
The open neutral condition, in distribution networks, can cause significant damage to customer installations. Due to this, the continuity of the neutral conductor is important to the power utilities. In this paper, a power flow algorithm for three-phase four-wire distribution networks with protective multiple earthing (PME), during an open neutral condition, is presented. This algorithm is based on a modified backwards-forwards technique. Additionally, the return current flow is explicitly modeled. Results from three different distribution feeders with different load unbalance and topology are presented and discussed. Furthermore, the effects of the grounding resistances, the load model (constant admittance or constant power), and the neutral breakage point (abruption point) on the voltage levels, are investigated.
Keywords :
earthing; load flow; power distribution protection; PME distribution systems; abruption point; constant admittance; constant power; customer installations; distribution feeders; grounding resistances; load model; load unbalance; modified backward-forward technique; neutral breakage point; neutral conductor; open neutral condition; power flow; power flow algorithm; power utilities; protective multiple earthing; return current flow; three-phase four-wire distribution networks; voltage levels; Grounding; Harmonic analysis; Load flow; Power system harmonics; Distribution feeders; load unbalance; open neutral; power flow; protective multiple earthing;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2012.2215967
Filename :
6317212
Link To Document :
بازگشت