DocumentCode :
502261
Title :
Application of TCSC to restore directional overcurrent relay coordination in systems with distributed generation
Author :
Khederzadeh, Mojtaba
Author_Institution :
Power & Water University of Technology (PWUT) - IRAN
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
In this paper a new approach is proposed to mitigate the directional overcurrent relay coordination problem, which arises from connecting distributed generation (DG) in looped power systems. It is based on the implementation of Thyristor Controlled Series Capacitor (TCSC) operating in fault current limiting mode to limit the fault current contribution from DG. Hence, the integrity of relay settings is preserved in emergencies. The original relay coordination is restored if the penetration level of DG is kept at a specified level. By the proposed method, the penetration level of DG is not a limiting factor anymore. The required TCSC inductive impedance beyond the penetration level of DG is indicated.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255672
Link To Document :
بازگشت