DocumentCode
502277
Title
Real-time voltage control integrated in DMS
Author
Svenda, Goran ; Strezoski, Vladimir ; Simendic, Zoran ; Mijatovic, Vidoje
Author_Institution
University of Novi Sad, Serbia
fYear
2009
fDate
8-11 June 2009
Firstpage
1
Lastpage
4
Abstract
The paper deals with the real time optimal voltage control integrated into contemporary Distribution Management Systems. The voltage profile of the entire distribution network is the optimization objective. Tap changer positions of all remotely controlled under load tap changing transformers are control variables. The optimization procedure is based on the results of the real time distribution state estimation running. The quality of the developed voltage control is quantified with the sum of squares of the deviations of voltages on low voltage busbars of the network distribution transformers. The presented results prove that this quality is significantly better than the quality of the network voltage profiles achieved by the application of the classic voltage control. The results are verified in several real-life distribution networks. The paper offers the results of the voltage control verification in the distribution network of the city of Sombor, the branch of the Electric Power Distribution Utility Elektrovojvodina, Novi Sad, Serbia.
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location
Prague, Czech Republic
ISSN
0537-9989
Print_ISBN
978-1-84919126-5
Type
conf
Filename
5255688
Link To Document