• DocumentCode
    502309
  • Title

    Neutral earthing reactors in overhead distribution networks

  • Author

    Pinto De Sa, Jose ; Louro, Miguel ; Freitas, Pedro

  • Author_Institution
    Instituto Superior T??cnico, Portugal
  • fYear
    2009
  • fDate
    8-11 June 2009
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Artificial Neutral Points made by oil-immersed reactors, particularly zigzag inductances, have been applied to limit earth fault currents in many MV distribution networks. ANPs can be overstressed both mechanically and thermally and a number of failures have been reported, particularly in overhead networks. A thermal analysis is performed which shows that present Standards requirements can underestimate the thermal stress due to fault conditions persisting for hours in some networks. A few approaches to this problem are reviewed and a new preventive protective solution is proposed.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
  • Conference_Location
    Prague, Czech Republic
  • ISSN
    0537-9989
  • Print_ISBN
    978-1-84919126-5
  • Type

    conf

  • Filename
    5255721