DocumentCode :
502345
Title :
Experimental model for diagnosing on-load tap changer contact aging with dynamic resistance measurements
Author :
Erbrink, Jur ; Gulski, Edward ; Smit, Johan ; Leich, Rory
Author_Institution :
Seitz Instruments AG, Switzerland
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
It is known that many failures of power transformers are related to aging effects of the on-load tap changer. Especially the OLTC contacts are prone to several aging mechanisms. To understand the aging mechanisms and to develop knowledge rules to interpret different failure mechanisms a test model has been developed. The effect of the several aging stages of tap changer change-over selector contacts on dynamic resistance measurements (DRM) has been considered, by several experiments with aged tap changer contacts. These aging phases include clean contacts, contacts with an oil film layer and contacts with coking. Based on these experiments it is shown that the DRM method is very sensitive to aged change-over selector contacts of an on-load tap changer. In addition to laboratory experiments, the same measurements are performed on naturally aged change-over selector contacts at a Dutch utility. This change-over selector was accessible so the physical status of the tap changer contacts can be compared with the measurement results.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255757
Link To Document :
بازگشت