DocumentCode :
502533
Title :
Confirming the reliability and safety of MV distribution network including DG applying protection applications for earth faults
Author :
Nikander, Ari
Author_Institution :
Finland
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
4
Abstract :
The paper describes the effects of distributed generation on the earth fault protection of a medium voltage feeder and protection coordination. Neutral isolated and compensated systems were considered. The aim was to investigate the behaviour of the production unit during automatic reclosings, especially as regards electrical safety. Methods possibly feasible for clearing a temporary earth fault without voltage break were considered. Thus disturbances affecting production and customers are less than with automatic reclosings. The method of the study was dynamic simulation of the earth faults in medium voltage system. The network model including a wind power plant was implemented applying PSCAD™ simulation software.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 1, 2009. CIRED 2009. 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
ISSN :
0537-9989
Print_ISBN :
978-1-84919126-5
Type :
conf
Filename :
5255946