DocumentCode :
509689
Title :
Power frequency overvoltages generated by solar plants
Author :
Pazos, F.J.
Author_Institution :
Iberdrola Distrib. Electr., Valencia, Spain
fYear :
2009
fDate :
8-11 June 2009
Firstpage :
1
Lastpage :
1
Abstract :
A new kind of overvoltage, not covered by present standards, has been detected in solar plants when switching the inverters off. This power frequency overvoltage can be transmitted to the MV network, giving rise to damages to some pieces of low voltage electronic equipment. This phenomenon has been investigated in the field, testing several inverters in different solar plants, where the overvoltages, as well as the damages in revenue meters, have been reproduced and recorded. It has been proved that some inverter configurations are more prone to create severe overvoltages than other. In addition, some solutions have been tested.
Keywords :
electronic equipment testing; fault diagnosis; invertors; solar power stations; MV network; inverters testing; low voltage electronic equipment; power frequency overvoltages; revenue meters; solar plants;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution - Part 2, 2009. CIRED 2009. The 20th International Conference and Exhibition on
Conference_Location :
Prague
Print_ISBN :
978-1-84919-160-9
Type :
conf
Filename :
5371242
Link To Document :
بازگشت