Title :
Testing distribution switchgear for partial discharge
Author :
Davies, Neil ; Goldthorpe, Simon
Author_Institution :
EA Technology Ltd, UK
Abstract :
• General correlation between Relative Humidity in substation and presence of Surface PD Activity - 60% RH triggered discharge early stages • Ultrasonic noise level does not continue to increase as equipment progresses towards failure • Level of discharge measured in pC had no discernible rise as it progressed to failure - Quantifying seriousness through ultrasonic level or pC level for surface discharge activity almost impossible • Switching is a critical time - Safety implications
Conference_Titel :
Electricity Distribution - Part 2, 2009. CIRED 2009. The 20th International Conference and Exhibition on
Conference_Location :
Prague, Czech Republic
Print_ISBN :
978-1-84919-160-9