  • Abstract
    This paper presents in this study a control algorithm to compensate harmonic current and reactive power simultaneously in 3 phase, where 3-wire and 4-wire non-linear loads. If the utility voltage is distorted, active power filter (APF) allows similar level of distortion in the compensated source current. Therefore, the resultant source currents have the same waveform as that of the supply voltage, thereby attributing the responsibility of utility and customer at the point of common coupling (PCC). Due to similar shape of the source voltage and currents, reactive power is compensated completely. The research is provided by a simulation study to verify the proposed algorithm(s).
  • Keywords
    active filters; compensation; distortion; electric current control; power factor; power harmonic filters; reactive power control; voltage control; common coupling point; customer unity power factor; harmonic compensation; reactive power compensation; shunt active power filter; source current compensation; source voltage distortion; Active filters; Harmonic distortion; Power harmonic filters; Power supplies; Power system harmonics; Reactive power; Reactive power control; Shape; Variable speed drives; Voltage; Active power filter; harmonic and reactive power compensation; ideal and distorted mains voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Systems Conference, 2006. MEPCON 2006. Eleventh International Middle East
  • Conference_Location
    El-Minia
  • Print_ISBN
    978-1-4244-5111-1
  • Type

    conf

  • Filename
    5372346