DocumentCode :
509878
Title :
High impedance fault detection based on wavelet transform and Prony´s method
Author :
ElRefaie, H.B.
Author_Institution :
Electr. Eng. Dept., Alexandria Univ., Alexandria, Egypt
Volume :
1
fYear :
2006
fDate :
19-21 Dec. 2006
Firstpage :
103
Lastpage :
111
Abstract :
A novel method for high impedance fault (HIP) detection based on wavelet transform and Prony´s method is presented. Using this method, HIFs can be discriminated from capacitor switching, transformer inrush current, and arc furnace. Wavelet transform is used for the decomposition of current signals and detecting disturbance resulting from either faults or normal switching currents. Prony´s method is used for estimating frequency, magnitude, phase, and damping presented in signals. Based on Prony´s estimation it is possible to distinguish between HIFs and normal switching. HIF and transient data was acquired from ATP-EMTP program. Results show that the proposed procedure is efficient in identifying HIFs from other even.
Keywords :
EMTP; capacitor switching; fault diagnosis; power distribution faults; wavelet transforms; ATP-EMTP program; HIF; Prony´s method; arc furnace; capacitor switching current; current signal decomposition; high impedance fault detection; transformer inrush current; wavelet transform; Capacitors; Fault detection; Frequency estimation; Furnaces; Hip; Impedance; Phase estimation; Signal detection; Surges; Wavelet transforms;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Systems Conference, 2006. MEPCON 2006. Eleventh International Middle East
Conference_Location :
El-Minia
Print_ISBN :
978-1-4244-5111-1
Type :
conf
Filename :
5372375
Link To Document :
بازگشت