DocumentCode
510951
Title
Measured results of flashover characteristics of distribution line insulators for sustaining insulated cable
Author
Sekioka, S. ; Miyazaki, T. ; Okabe, S.
Author_Institution
Shonan Inst. of Technol., Fujisawa, Japan
fYear
2008
fDate
7-12 Sept. 2008
Firstpage
301
Lastpage
304
Abstract
This paper describes experimental results of flashover characteristics of a medium voltage insulator to support an insulated cable using an impulse voltage generator. This experiment is targeted for direct lightning strokes to a distribution line. The lightning impulse voltage is applied to a cross arm to represent the direct lightning stroke. A flashover on the insulator occurs from the arm to the cable at first, and then the surface discharge develops along the cable. If the applied voltage is sufficiently high, the breakdown in the insulation of the cable occurs. This final stage corresponds to a line fault.
Keywords
flashover; insulator testing; lightning protection; power cable insulation; power cable testing; power distribution faults; power distribution lines; power overhead lines; pulse generators; surface discharges; direct lightning strokes; distribution line insulators; flashover characteristics; impulse voltage generator; insulated cable; lightning impulse voltage; lightning protection; medium voltage insulator; power line fault; surface discharge; Cable insulation; Cable shielding; Conductors; Dielectrics and electrical insulation; Flashover; Lightning; Power cable insulation; Power cables; Surface discharges; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
Conference_Location
Cardiff
Print_ISBN
978-0-9558052-0-2
Type
conf
Filename
5379226
Link To Document