DocumentCode
510985
Title
Calculation of overpressure in the surroundings of fault arcs in SF6 -air mixtures
Author
Anantavanich, K. ; Pietsch, G.J.
Author_Institution
Inst. for High Voltage Technol., RWTH Aachen Univ., Aachen, Germany
fYear
2008
fDate
7-12 Sept. 2008
Firstpage
165
Lastpage
168
Abstract
Because of the excellent insulating and quenching properties of SF6 it is used e.g. in compact switchgear installations. In the case of internal arcing, hot SF6 escapes from the faulty compartment carrying energy into the air surroundings, which causes overpressure within the switchgear and the switchgear building. During this process the SF6 concentration varies continuously. In order to calculate the pressure rise the gas properties of the varying SF6-air mixture must be included in the calculation procedure. A calculation model has been developed, which considers the changing gas properties according to the varying SF6 concentration. The model is evaluated by comparing experimental with calculation results.
Keywords
SF6 insulation; arcs (electric); switchgear insulation; SF6 quenching properties; SF6-air mixtures; fault arc surrounding; overpressure calculation; switchgear installations; Arc discharges;
fLanguage
English
Publisher
ieee
Conference_Titel
Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
Conference_Location
Cardiff
Print_ISBN
978-0-9558052-0-2
Type
conf
Filename