Title :
Discussions on post arc current of a CO2 circuit breaker
Author :
Nishiwaki, S. ; Koshizuka, T. ; Uchii, T. ; Kawano, H.
Author_Institution :
Toshiba Corp., Kawasaki, Japan
Abstract :
It has been observed in our tests that the post arc current near the breaking limit of a CO2 circuit breaker is 10 A or more, and the post arc current of a SF6 circuit breaker is approximately 0.3 A. We explain this major difference in the post arc current with calculations using two serially-connected arc models. We prove that the arc characteristic of a relatively longer time domain up to the extinction peak for a CO2 circuit breaker and that of a short time domain from the extinction peak until the current zero point for a SF6 circuit breaker have great effects on breaking performance.
Keywords :
SF6 insulation; circuit breakers; circuit-breaking arcs; gas blast circuit breakers; CO2 circuit breaker; SF6 circuit breaker; current zero point; post arc current; serially-connected arc models calculation; Circuit breakers; Circuit testing; Current measurement; Equations; Linear approximation; Substations; Sulfur hexafluoride; Time measurement; Voltage;