• DocumentCode
    511048
  • Title

    Prebreakdown phenomena in CO2/SF6 under very fast transients in non-uniform field

  • Author

    Pfeiffer, W. ; Kuzishin, N. ; Zhurkov, M.

  • Author_Institution
    Lab. for Electr. Meas. Tech., Darmstadt Univ. of Technol., Darmstadt, Germany
  • fYear
    2008
  • fDate
    7-12 Sept. 2008
  • Firstpage
    537
  • Lastpage
    540
  • Abstract
    The Gas Insulated Line (GIL) is a reliable system for electrical energy transport. One of the important parts of the GIL is the insulating gas that can be stressed not only with lightning impulses, but also with very fast transients (VFT) if a busduct connector is being closed or opened. An alternative gaseous medium is needed in order to substitute completely or at least partially the expensive gas SF6. This aspect is also important with respect to environmental considerations (greenhouse effect). As an alternative, CO2/SF6 mixtures are chosen. Prebreakdown phenomena were investigated for 1,33 MHz of VFT, positive polarity, non-uniform field distribution with admixtures of SF6 to CO2 of 10 %, 20 %, 30 %, 40 % and a pressure range from 0,1 to 0,8 MPa.
  • Keywords
    SF6 insulation; electric breakdown; electric connectors; environmental management; insulator testing; power system transients; busduct connector; electrical energy transport; environmental considerations; fast transients; gas insulated line; nonuniform field distribution; positive polarity; prebreakdown phenomena; Breakdown voltage; Cathodes; Electric breakdown; Electrodes; Gas insulated transmission lines; Gas insulation; Image intensifiers; Needles; Sulfur hexafluoride; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
  • Conference_Location
    Cardiff
  • Print_ISBN
    978-0-9558052-0-2
  • Type

    conf

  • Filename
    5379380