• DocumentCode
    523652
  • Title

    Calculation of the Filter Parameters for the Aluminum Electrolyzation Rectifier

  • Author

    Yuquan, Ma ; Lihong, Zhang ; Shufen, Han

  • Author_Institution
    Hebei Normal Univ. of Sci. & Technol., Qinhuanggao, China
  • Volume
    1
  • fYear
    2010
  • fDate
    11-12 May 2010
  • Firstpage
    906
  • Lastpage
    910
  • Abstract
    In this paper, the rectifier transformer third winding to install high-pass filter have been studied, and the calculating method of the high-pass filter parameters have been put forward. The power factor and the filter parameter of three series rectifier unit in a company are calculated, then it’s discovered that the practical operating parameter tallies with theoretical result and the practical power factor fits with the theory in one of the series of filters, and this attain the system requisition, so then demonstrates the parameter calculation method in this paper is correct. It is suggested that the capacitance capacity of the high-pass filter of the third winding in aluminum electrolyzation rectifier unit should be calculated according to meeting to the displacement factor compensation requisition, that is, cut-off frequency: 3th harmonic, resonance frequency: 7th harmonic, quality factor: 5 or so, m: 0.2 or so, resistance: ≤10Ω. The greater the filtering resistance, the stronger the harmonic impedance, which will affect the harmonic filtering effect.
  • Keywords
    Aluminum; Capacitance; Cutoff frequency; Filtering theory; Power harmonic filters; Q factor; Reactive power; Rectifiers; Resonance; Resonant frequency; Filter; Harmonic; PowerFactor; Rectification;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Intelligent Computation Technology and Automation (ICICTA), 2010 International Conference on
  • Conference_Location
    Changsha, China
  • Print_ISBN
    978-1-4244-7279-6
  • Electronic_ISBN
    978-1-4244-7280-2
  • Type

    conf

  • DOI
    10.1109/ICICTA.2010.500
  • Filename
    5522763