DocumentCode
533487
Title
“Control of an SVC for the load balancing and power factor correction with a new algorithm based on the power analysis”
Author
Mokhtari, Maghsood
Author_Institution
Urmia University/ Department Of Electrical Engineering, Iran
fYear
2010
fDate
14-15 Sept. 2010
Firstpage
1
Lastpage
1
Abstract
A compact algorithm based on power analysis for reactive power compensation as well as load balancing through the static var compensator (SVC) in three-phase three-wire system is developed in this paper. The structure of the SVC is thyristor controlled reactors with fixed capacitors (TCR-FC). By the proposed algorithm the required compensation susceptances for each phase of the SVC is obtained from a very simple function of voltage and reactive power signals which are measured from the network. The salient feature associated with the proposed method is that the circuit representation of system load is not required and the load is recognized just by its active and reactive consumptions. The load´s type and connection, hence, do not matter and this method is valid for the case of active loads too. The validity and performance of the new approach are analyzed via a numerical example and the obtained simulation results are thoroughly discussed.
Keywords
Load Balancing; Power Analysis; Power Factor Correction; Reactive Power Compensation; Static Var Compensator (svc);
fLanguage
English
Publisher
ieee
Conference_Titel
Power Quality Conference (PQC), 2010 First
Conference_Location
Tehran, Iran
Print_ISBN
978-1-4244-8483-6
Electronic_ISBN
978-964-463-063-7
Type
conf
Filename
5624696
Link To Document