Abstract :
This paper has investigated lightning surges on a cable installed along a transmission tower, which becomes quite common in Japan, considering phase wires and ground wires based on a field measurement and EMTP simulations. It is found that the tower top and bottom voltages are higher in the case of the metallic sheath of the cable being grounded to the tower arm than those in the case of the sheath connected to a grounding lead. However, a voltage difference between the tower and the cable at the tower bottom is smaller in the former. It should be noted that surge voltages are much lower when phase and ground wires are considered than the voltages when the wires are neglected.
Keywords :
EMTP; earthing; electric field measurement; lightning; lightning protection; power cables; power transmission lines; power transmission protection; surges; EMTP simulation; Japan; cable installation; field measurement; ground wire; grounding lead; lightning surge; metallic sheath; phase wire; surge voltage; tower arm; tower bottom voltage; tower top voltage; transmission tower; Wire; EMTP; cable; field test; grounding lead; lightning surge; tower;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference (UPEC), 2010 45th International
Conference_Location :
Cardiff, Wales
Print_ISBN :
978-1-4244-7667-1
Type :
conf
Filename :
5649944
Link To Document :
بازگشت