• DocumentCode
    538988
  • Title

    A new approach to harmonic allocation for MV installations

  • Author

    Gosbell, V.J. ; Barr, R.A.

  • Author_Institution
    Univ. of Wollongong, Wollongong, NSW, Australia
  • fYear
    2010
  • fDate
    5-8 Dec. 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Distributors need to allocate a maximum allowed level of harmonic current to MV customers to keep voltage distortion acceptable. The paper describes a new approach, based on the concept of voltage droop, requiring much less calculation and data than required by the present approach based on an IEC technical report. The discrepancy between the new method and the present is studied by comparing some carefully selected scenarios. It is shown that the proposed method gives results within 20% of the standards-based approach which makes it a very attractive alternative for harmonic allocation.
  • Keywords
    power distribution; power system harmonics; IEC technical; MV installations; distribution systems; harmonic allocation; voltage distortion; voltage droop; Guidelines; Harmonic analysis; IEC; Impedance; Power system harmonics; Resource management; IEC standards; distribution systems; harmonic allocation; harmonics; voltage droop;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Universities Power Engineering Conference (AUPEC), 2010 20th Australasian
  • Conference_Location
    Christchurch
  • Print_ISBN
    978-1-4244-8379-2
  • Electronic_ISBN
    978-1-4244-8380-8
  • Type

    conf

  • Filename
    5710744