System Thevenin impedance estimation through on-load tap changer action
Author
Bahadornejad, M. ; Nair, N.K.C.
Author_Institution
Dept. of Electr. Eng., Power & Water Univ. of Technol., Tehran, Iran
fYear
2010
fDate
5-8 Dec. 2010
Firstpage
1
Lastpage
5
Abstract
Many of power system studies are based on a two-bus equivalent system where the supply system is represented by its Thevenin equivalent seen from the terminals of the bus of interest. In this paper a novel method is developed to estimate power system Thevenin impedance that uses the changes of the load bus voltage and current, caused by the on-load tap changer (OLTC) action. It is shown that the changes in the load voltage and current in the primary side of OLTC can be used to estimate the system Thevenin impedance. The proposed method is confirmed by simulation.
Keywords
on load tap changers; power system simulation; OLTC action; load bus voltage; on load tap changer action; power system Thevenin impedance estimation; power system study; two-bus equivalent system; Computer aided software engineering; Delay effects; Impedance; Induction motors; Load modeling; Power systems; Voltage measurement; on-load tap changer; power system modeling; smart grids; thevenin impedance estimation;