• DocumentCode
    539816
  • Title

    Protection against Reactor Inter-Turn Fault with Shunt Capacitance Compensator Based on Voltage Ratio

  • Author

    Menghe, Li ; Shenghui, Pan ; Fan, Zhang ; Chuan, Lin

  • Author_Institution
    Dept. of Electr. Inf. & Control Eng., Guangxi Univ. of Technol., Liuzhou, China
  • Volume
    2
  • fYear
    2011
  • fDate
    6-7 Jan. 2011
  • Firstpage
    936
  • Lastpage
    938
  • Abstract
    Shunt capacitance compensator is the important equipment of power traction system in electrified railway. The series-wound reactor on the compensator is lack of necessary protection against inter-turn fault. The voltage ratio of the capacitor and reactor will change when the fault occurs. With consideration of characteristics of power traction system in electrified railway, this paper proposes a new shunt compensation protection against reactor inter-turn fault based on the voltage ratio. The simulation on ATP and calculation on MATLAB show that the protection against inter-turn fault of reactor, based on voltage ratio, can make correct judgment to this kind of fault quickly. This kind of protection has been applied to a substation in Beijing-Qinhuangdao railway and has run well until now.
  • Keywords
    capacitors; substation protection; traction power supplies; Beijing Qinhuangdao railway; electrified railway; power traction system; reactor inter turn fault; series wound reactor; shunt capacitance compensator; substation; voltage ratio; Capacitance; Capacitors; Circuit faults; Harmonic analysis; Inductors; Rail transportation; Shunt (electrical); Electrified Railway; Inter-turn Fault; Shunt Capacitance Compensator; Voltage Ratio Protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Measuring Technology and Mechatronics Automation (ICMTMA), 2011 Third International Conference on
  • Conference_Location
    Shangshai
  • Print_ISBN
    978-1-4244-9010-3
  • Type

    conf

  • DOI
    10.1109/ICMTMA.2011.516
  • Filename