• DocumentCode
    541223
  • Title

    Comparison and selection of high-voltage large-capacity D-STATCOM main circuit

  • Author

    Yang, Zhen-yu ; Xu, Sheng ; Xing-tao Xu

  • Author_Institution
    Substation Oper. Center, Changzhou Power Supply Co., Changzhou, China
  • fYear
    2010
  • fDate
    13-16 Sept. 2010
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    In view of analysis and comparison of present high-voltage large-capacity D-STATCOM circuit structure, especially advantages and disadvantages of Δ-cascaded structure and Y-cascaded structure, then it proposes and describes a Y-cascaded structure, the link of which is composed of two back-to-back H converters. Current compensation algorithm based on coordinate αβ conversion, fault links bypass tolerance, and its correlative CPS-SPWM are proposed respectively, the experimental results of 1.14kV/100kVA prototype testify the validity and the effectivity of the proposed structure and algorithm.
  • Keywords
    compensation; static VAr compensators; Δ-cascaded structure; CPS-SPWM; Y-cascaded structure; apparent power 100 kVA; back-to-back H converters; current compensation algorithm; fault links bypass tolerance; high-voltage large-capacity D-STATCOM main circuit; voltage 1.14 kV; Automatic voltage control; Circuit faults; Fault tolerance; Inverters; Joints; Periodic structures; Voltage measurement; D-STATCOM; Y-cascaded structure; fault-tolerance; neutral shift;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2010 China International Conference on
  • Conference_Location
    Nanjing
  • Print_ISBN
    978-1-4577-0066-8
  • Type

    conf

  • Filename
    5735926