Abstract
Knowing the state of degradation of electrical insulation materials is important for any type of equipment, but it is imperative in the case of equipment for nuclear plants. A study was conducted to evaluate the use of oxygen under pressure to accelerate thermo-oxidative degradation rate in EVA compound used as cable jacket. In this paper are presented the results of estimating the state of deterioration of insulating EVA compound subjected to accelerated aging simple and combined, thermal and oxygen pressure. Evaluation of degradation was performed using DSC method, and verification of results was done by determining the elongation at break. The paper concludes that the use of DSC allows accurate estimation of activation energy and estimate the lifetime of the material.
Keywords
ageing; cable sheathing; insulation; nuclear power stations; power apparatus; power cables; DSC method; EVA compound insulation; accelerated aging; activation energy; assessment condition degradation; cable jacket; electrical insulation materials; nuclear plant equipment; oxygen pressure; thermal pressure; thermooxidative degradation rate; Aging; Cable shielding; Compounds; Degradation; Heating; Materials; Oxidation;
fLanguage
English
Publisher
ieee
Conference_Titel
Advanced Topics in Electrical Engineering (ATEE), 2011 7th International Symposium on
Conference_Location
Bucharest
ISSN
2068-7966
Print_ISBN
978-1-4577-0507-6
Type
conf
Filename
5952209
Link To Document