• DocumentCode
    547112
  • Title

    Assessment condition degradation of the EVA compound used as cable jacket

  • Author

    George, Mares ; Catalin, Rusu-Zagar ; Simona, Pasareanu ; Gilda, Rusu-Zagar

  • Author_Institution
    S.C. EUROTEST S.A., Bucharest, Romania
  • fYear
    2011
  • fDate
    12-14 May 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Knowing the state of degradation of electrical insulation materials is important for any type of equipment, but it is imperative in the case of equipment for nuclear plants. A study was conducted to evaluate the use of oxygen under pressure to accelerate thermo-oxidative degradation rate in EVA compound used as cable jacket. In this paper are presented the results of estimating the state of deterioration of insulating EVA compound subjected to accelerated aging simple and combined, thermal and oxygen pressure. Evaluation of degradation was performed using DSC method, and verification of results was done by determining the elongation at break. The paper concludes that the use of DSC allows accurate estimation of activation energy and estimate the lifetime of the material.
  • Keywords
    ageing; cable sheathing; insulation; nuclear power stations; power apparatus; power cables; DSC method; EVA compound insulation; accelerated aging; activation energy; assessment condition degradation; cable jacket; electrical insulation materials; nuclear plant equipment; oxygen pressure; thermal pressure; thermooxidative degradation rate; Aging; Cable shielding; Compounds; Degradation; Heating; Materials; Oxidation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Advanced Topics in Electrical Engineering (ATEE), 2011 7th International Symposium on
  • Conference_Location
    Bucharest
  • ISSN
    2068-7966
  • Print_ISBN
    978-1-4577-0507-6
  • Type

    conf

  • Filename
    5952209