Title :
Harmonics reduction in high-efficiency operation of double-conversion UPS
Author :
Giuntini, Lorenzo
Author_Institution :
GE Consumer & Ind. SA, Riazzino, Switzerland
fDate :
Aug. 30 2011-Sept. 1 2011
Abstract :
UPS are used to protect critical loads, and double-conversion is often the preferred choice. While providing optimum protection, this topology offers limited efficiency. Some double-conversion UPS feature a high-efficiency (ECO) mode, with the load normally fed via the bypass path. In this operating mode, load current harmonics may be let through towards the utility, and may induce a high load on the neutral conductor. In this context, this paper discusses Advanced ECO Mode topologies that reduce neutral current and mitigate harmonics resulting from non-linear or unbalanced load.
Keywords :
power supply quality; uninterruptible power supplies; advanced ECO mode topologies; double-conversion UPS; harmonics reduction; high-efficiency operation; load current harmonics; neutral conductor; Conductors; Harmonic analysis; Inverters; Power system harmonics; Topology; Uninterruptible power systems; Windings; Efficiency; Harmonics; Power Quality; Uninterruptible Power Supply (UPS);
Conference_Titel :
Power Electronics and Applications (EPE 2011), Proceedings of the 2011-14th European Conference on
Conference_Location :
Birmingham
Print_ISBN :
978-1-61284-167-0
Electronic_ISBN :
978-90-75815-15-3