• DocumentCode
    558412
  • Title

    A Hierarchical Analysis of phasor measurement unit placement optimization in transmission network

  • Author

    Zhong, Jiangxia ; Wong, K.L.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., RMIT Univ., Melbourne, VIC, Australia
  • fYear
    2011
  • fDate
    25-28 Sept. 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents a new phasor measurement unit (PMU) placement algorithm based on Hierarchical Analysis, a hybrid algorithm combining the breadth-first algorithm (BFA) and greedy algorithm. With the optimized number of PMU, the system is to maintain full network view during normal operation with and without conventional zero-injection effect. The IEEE standard 14-, 30-, 57- and the New England 39-bus test systems are investigated. Based on the comparison of the proposed method in this paper with other published methods, the proposed method has achieve good results with minimal PMU required and maximum system observability redundancy index (SORI).
  • Keywords
    IEEE standards; greedy algorithms; phasor measurement; transmission networks; IEEE standard; New England 39-bus test systems; PMU; SORI; breadth-first algorithm; greedy algorithm; hierarchical analysis; phasor measurement unit; placement optimization; system observability redundancy index; transmission network; Algorithm design and analysis; Computer aided software engineering; Greedy algorithms; Indexes; Observability; Phasor measurement units; Redundancy; Breadth-First Algorithm; Greedy Algorithm; Maximum Redundancy; Network Observability; Phasor Measurment Unit;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Universities Power Engineering Conference (AUPEC), 2011 21st Australasian
  • Conference_Location
    Brisbane, QLD
  • Print_ISBN
    978-1-4577-1793-2
  • Type

    conf

  • Filename
    6102542