  • Abstract
    The presence of Corrosive sulphur in mineral transformer oil affects the performance of insulation system of transformers. In this paper results of experimental investigations carried out on voltage current characteristics and insulation resistance of paper oil insulation in presence of copper sulphide are presented and discussed. A model for copper sulphide migration is proposed to explain the increase in leakage current and reduction in insulation resistance. Existence of two regions in voltagecurrent characteristics, one dependent on the insulation properties of paper oil insulation and other due to semi-conducting copper sulphide is discussed and explained.
  • Keywords
    copper compounds; leakage currents; paper; sulphur; transformer oil; copper sulphide effect; copper sulphide migration; corrosive sulphur; insulation resistance; insulation resistance reduction; leakage current; mineral transformer oil; paper oil insulation; transformer insulation system; voltage current characteristic; Conductors; Copper; Discharges (electric); Electrodes; Oil insulation; Power transformer insulation; Breakdown voltage; copper corrosion; insulation resistance; paper insulation; power transformers;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004408
  • Filename
    7033431