Experimental simulation of effects of copper sulphide on insulation system of transformers
Author :
Khan, Faheem Ahmed ; Rajan, J. Sundara
Author_Institution :
Dept. of Electr. & Electron. Eng., Ghousia Coll. of Eng., Ramanagaram, India
Volume :
22
Issue :
1
fYear :
2015
fDate :
Feb. 2015
Firstpage :
571
Lastpage :
580
Abstract :
The presence of Corrosive sulphur in mineral transformer oil affects the performance of insulation system of transformers. In this paper results of experimental investigations carried out on voltage current characteristics and insulation resistance of paper oil insulation in presence of copper sulphide are presented and discussed. A model for copper sulphide migration is proposed to explain the increase in leakage current and reduction in insulation resistance. Existence of two regions in voltagecurrent characteristics, one dependent on the insulation properties of paper oil insulation and other due to semi-conducting copper sulphide is discussed and explained.
Keywords :
copper compounds; leakage currents; paper; sulphur; transformer oil; copper sulphide effect; copper sulphide migration; corrosive sulphur; insulation resistance; insulation resistance reduction; leakage current; mineral transformer oil; paper oil insulation; transformer insulation system; voltage current characteristic; Conductors; Copper; Discharges (electric); Electrodes; Oil insulation; Power transformer insulation; Breakdown voltage; copper corrosion; insulation resistance; paper insulation; power transformers;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on