DocumentCode
570039
Title
State estimation in electric distribution networks in presence of distributed generation using the PMUs
Author
Haghifam, M. ; Haghifam, Mahmood-Reza ; Chabok, B.S.
Author_Institution
Sharif Univ. of Technol., Tehran, Iran
fYear
2012
fDate
29-30 May 2012
Firstpage
1
Lastpage
4
Abstract
Regarding the high cost of PMU units, optimal placement and minimizing of their numbers are of great importance. Also, this paper proposes a new procedure for determining the optimal placement and less numbers of PMUs in distribution network based on the best state estimation criterion. For DSE solution, combination of Nelder-Mead (NM) simplex search and Ant Colony Optimization (ACO) algorithm have been used. The hybrid method can estimate voltage phasor at each node by minimizing difference between measured and calculated values of state variables and also, it can guarantee observability of distribution system under normal operation conditions. To demonstrate the effectiveness of new procedure, simulation studies are applied on 30-bus radial test feeder. Finally, achievement results for convergence characteristic of DSE solution and estimation error of state variables with regard to the optimal placement and numbers of PMUs in distribution test feeder have been presented.
Keywords
ant colony optimisation; distributed power generation; distribution networks; 30-bus radial test feeder; ACO algorithm; NM simplex search; Nelder-Mead simplex search; PMU unit; ant colony optimization algorithm; distributed generation; distribution test feeder; electric distribution networks; optimal placement; state estimation; voltage phasor estimation;
fLanguage
English
Publisher
iet
Conference_Titel
Integration of Renewables into the Distribution Grid, CIRED 2012 Workshop
Conference_Location
Lisbon
Electronic_ISBN
978-1--84919-628-4
Type
conf
DOI
10.1049/cp.2012.0754
Filename
6302386
Link To Document