DocumentCode
570393
Title
Insulation status detection on the high voltage bushing by FRA method
Author
Chunyan, Zang ; Jinxing, Gan ; Dexin, Nie ; Zhenbo, Du ; Zhenpeng, Tang ; Xiaoqiang, Deng
Author_Institution
Inst. of Electr. & Electron. Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
fYear
2012
fDate
21-24 May 2012
Firstpage
1
Lastpage
4
Abstract
This paper mainly discusses the mechanism for FRA method on bushing insulation detection. It builds several RC models of the bushing instruction in MATLAB, as well as does some simulation work to observe the change of the FRA curve with different parameters. It also takes the influence of the valve wire into consider and get some useful conclusions. Simulation results show that the obvious indentation in the FRA curve will appear when the bushing has some insulation defects. The sum and change state of the indentation in FRA curve is related to the degree and relaxation polarization of the insulation defects of the bushing. It is found that the simulation and on-spot detection curves have tallies with each other, which verifies the feasibility of FRA method in this field.
Keywords
bushings; frequency response; insulation testing; FRA curve; MATLAB; RC models; bushing instruction; bushing insulation detection; frequency response analysis; high voltage bushing; indentation; insulation defects; insulation status detection; on-spot detection curves; relaxation polarization; Capacitance; Phase measurement; Resonant frequency; Wires; Bushing; FRA; Insulation detection; RC Model;
fLanguage
English
Publisher
ieee
Conference_Titel
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2012 IEEE
Conference_Location
Tianjin
Print_ISBN
978-1-4673-1221-9
Type
conf
DOI
10.1109/ISGT-Asia.2012.6303214
Filename
6303214
Link To Document