• DocumentCode
    572240
  • Title

    Modeling and Analysis of Stage Difference Coordination of Protective Devices in DC System

  • Author

    Song, Qiuchi ; Liu, Junyong ; Wei, Yu ; Zhang, Peng

  • Author_Institution
    Intell. Electr. Power Grid Key Lab., Sichuan Univ., Chengdu, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    For the current existing problems of modeling on stage different coordination, it analyzes the Ampere-second characteristic of the common DC circuit breakers, which must considers the dispersion characteristic. Through correcting the Ampere-second characteristic function by time-sharing coefficient, it can draw the Pre-acring Ampere-second curve and analyze the stage different coordination. On this basis, it developed the simulation software for the Guangdong power Grid Substation DC system, to calculate the limit electric current for the upstream-downstream breakers which is closer to the engineering actual current. It can improve the reliability of the substation DC systems, and provide the basis for choosing the DC circuit breakers and transforming the old station.
  • Keywords
    circuit breakers; power grids; reliability; substation protection; Ampere-second characteristic; DC circuit breakers; Guangdong; dispersion characteristic; limit electric current; power grid substation DC system; protective devices; reliability; stage difference coordination; time-sharing coefficient; Analytical models; Circuit breakers; Delay; Integrated circuit modeling; Substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307425
  • Filename