Energy efficient cooling in data center using optimization approach
Author
Nakamura, Masayuki ; Nakamura, Ryota ; Nishida, Ryuichi ; Takeuchi, Akira ; Tominaga, Tetsuya
Author_Institution
NTT Energy & Environ. Syst. Labs., Tokyo, Japan
fYear
2012
fDate
20-23 Aug. 2012
Firstpage
2103
Lastpage
2108
Abstract
This paper presents an optimal cooling approach to minimize the power consumption of computer room air conditioners in data centers. A temperature control experiment was conducted in a simulated data center. Based on the experimental data, temperature and power consumption models are introduced to formulate an optimization problem. The resulting coordinated control led to a power consumption reduction. The simulation results indicate that the proposed optimization approach resulted in 6% to 14% less power consumption than that of a baseline control.
Keywords
computer centres; cooling; minimisation; power aware computing; power consumption; computer room air conditioner; coordinated control; data center; energy efficient cooling; optimal cooling approach; optimization approach; power consumption minimisation; power consumption reduction; temperature control experiment; Cooling; Optimization; Power demand; Servers; Temperature distribution; Temperature measurement; data centers; energy efficiency; optimization; thermal control;