• DocumentCode
    577270
  • Title

    Measurement of the dielectric performance of an instrument transformer at different voltage and frequencies

  • Author

    Arikan, Orhan ; Kumru, Celal Fadil ; Kocatepe, Celal

  • Author_Institution
    Dept. of Electr. Eng., Yildiz Tech. Univ., Esenler, Turkey
  • fYear
    2012
  • fDate
    17-20 Sept. 2012
  • Firstpage
    451
  • Lastpage
    454
  • Abstract
    In this study, the capacity, tan delta and dielectric loss of an IVT are measured for different voltage levels and frequency values. The measurement process is realized for the isolation between the primary and secondary windings of a 10kV/0,1 kV nominal rated IVT. As a measurement device, CPC100/CP TD1, which is frequently preferred especially in field applications, is used. Results indicated that, the dissipation factor changes according to the voltage levels. When voltage level gets closer to nominal value or exceeds it, it is seen that tan delta value increases rapidly. Moreover, it is found that the rising frequency has a negative effect on the dielectric loss of the material as a result of the measurements at different frequency values between 50 Hz - 400 Hz.
  • Keywords
    dielectric losses; transformer windings; CPC100/CP TD1; IVT; dielectric loss; dielectric performance measurement; dissipation factor; frequency 50 Hz to 400 Hz; instrument transformer; measurement device; primary windings; secondary windings; tan delta; Dielectric loss measurement; Dielectric losses; Frequency measurement; Insulation; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2012 International Conference on
  • Conference_Location
    Shanghai
  • Print_ISBN
    978-1-4673-4747-1
  • Type

    conf

  • DOI
    10.1109/ICHVE.2012.6357030
  • Filename
    6357030