Measurement of the dielectric performance of an instrument transformer at different voltage and frequencies
Author
Arikan, Orhan ; Kumru, Celal Fadil ; Kocatepe, Celal
Author_Institution
Dept. of Electr. Eng., Yildiz Tech. Univ., Esenler, Turkey
fYear
2012
fDate
17-20 Sept. 2012
Firstpage
451
Lastpage
454
Abstract
In this study, the capacity, tan delta and dielectric loss of an IVT are measured for different voltage levels and frequency values. The measurement process is realized for the isolation between the primary and secondary windings of a 10kV/0,1 kV nominal rated IVT. As a measurement device, CPC100/CP TD1, which is frequently preferred especially in field applications, is used. Results indicated that, the dissipation factor changes according to the voltage levels. When voltage level gets closer to nominal value or exceeds it, it is seen that tan delta value increases rapidly. Moreover, it is found that the rising frequency has a negative effect on the dielectric loss of the material as a result of the measurements at different frequency values between 50 Hz - 400 Hz.
Keywords
dielectric losses; transformer windings; CPC100/CP TD1; IVT; dielectric loss; dielectric performance measurement; dissipation factor; frequency 50 Hz to 400 Hz; instrument transformer; measurement device; primary windings; secondary windings; tan delta; Dielectric loss measurement; Dielectric losses; Frequency measurement; Insulation; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location
Shanghai
Print_ISBN
978-1-4673-4747-1
Type
conf
DOI
10.1109/ICHVE.2012.6357030
Filename
6357030
Link To Document