DocumentCode :
577317
Title :
Failure evaluation model of oil-paper insulation under AC-DC combined voltages
Author :
Yan Wang ; Jian Li ; Yuming Zhao ; Zhiman He ; Sicheng Wu ; Lianwei Bao
Author_Institution :
State Key Lab. of Power Transm. Equip. & Syst. Security & New Technol., Chongqing Univ., Chongqing, China
fYear :
2012
fDate :
17-20 Sept. 2012
Firstpage :
396
Lastpage :
399
Abstract :
The insulation of windings connected with converter valves have to withstand AC, DC and repetitive impulse combined voltages in converter transformers. This paper presented the failure evaluation model by experimental research on electrical breakdown characteristics of oil-paper insulation under AC, DC and AC-DC combined voltages. Both short-time tests and constant-stress tests were carried out when the insulation system was subjected to different applied voltages. The breakdown strength and times-to-breakdown of oil-paper specimens have been investigated by tests. The inverse power model was presented by the weibull parameters which were estimated by the times-to-breakdown of specimens. Using the parameters of weibull model and inverse power model, the functions of failure evaluation model were calculated. It could establish the relationship between times, voltages and failure probability of insulation. And final evaluation results showed it was more effective than tradition failure model and weibull model. The DC component behavior in the insulation system has been analyzed and the influence of AC-DC combined voltages on insulation system was discussed.
Keywords :
AC-DC power convertors; Weibull distribution; failure analysis; power transformer insulation; transformer oil; transformer windings; AC-DC combined voltages; DC component behavior; Weibull model parameters; constant-stress tests; converter transformers; converter valves; electrical breakdown characteristics; failure evaluation model; insulation failure probability; inverse power model; oil-paper insulation; oil-paper specimen times-to-breakdown; repetitive impulse combined voltages; short-time tests; winding insulation; Breakdown voltage; Electric breakdown; Mathematical model; Oil insulation; Power transformer insulation; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location :
Shanghai
Print_ISBN :
978-1-4673-4747-1
Type :
conf
DOI :
10.1109/ICHVE.2012.6357133
Filename :
6357133
Link To Document :
بازگشت