Title :
A comparison of wind integration metrics in the Tasmanian context
Author :
Jones, Derek ; Negnevitsky, Michael ; Pasalic, Sead ; Haque, Md Enamul
Author_Institution :
Transend Networks, Hobart, TAS, Australia
Abstract :
Large-scale integration of wind into power grids can have significant impact on the system stability. The maximum amount of wind generation a particular grid can sustain is a function of many variables such as load, generation dispatch, wind generation technology and the flow across interconnectors. There have been several attempts at determining a simple empirical criterion for determining this limit in real time. Some in particular are the Irish System Non Synchronous Penetration (SNSP) and the Tasmanian Rate of Change of Frequency criteria. This paper compares the application of these two metrics. The situations in which each metric gives better performance are analysed. Finally, the direct application of each metric to the Tasmanian context is analysed.
Keywords :
power system stability; wind power plants; Irish SNSP; Irish system nonsynchronous penetration; Tasmanian context; generation dispatch; power grids; system stability; wind generation technology; wind large-scale integration; Context; Equations; Generators; HVDC transmission; Mathematical model; Measurement; Wind farms; rate of frequency change; wind integration metrics; wind power;
Conference_Titel :
Universities Power Engineering Conference (AUPEC), 2012 22nd Australasian
Conference_Location :
Bali
Print_ISBN :
978-1-4673-2933-0