Abstract :
Relationships between shaft voltages and static eccentricities are studied, theoretical analysis shows that shaft voltages are induced by the `distorted fluxes´ caused by static eccentricities, shaft voltages mainly contain odd harmonics, the harmonic amplitudes increase under greater eccentricities. Some new distorted flux hamonics appear when field windings interturn short circuit happens, the harmonic frequencies change with the generator pole-pair number, and amplitudes increase when the fault get worse. The following experimental work agrees with the theoretical predictions.
Keywords :
fault diagnosis; machine windings; shafts; turbogenerators; distorted flux harmonics; field winding interturn short circuit; generator pole-pair number; harmonic amplitudes; shaft voltage; static eccentricity; turbine generator fault diagnosis; Air gaps; Circuit faults; Coils; Generators; Harmonic analysis; Shafts; Windings; Current; Fault location; Generators; Grounding; Harmonic analysis; Monitoring; Rotors; Shafts; Signal detection; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting (IAS), 2012 IEEE
Conference_Location :
Las Vegas, NV
ISSN :
0197-2618
Print_ISBN :
978-1-4673-0330-9
Electronic_ISBN :
0197-2618
Type :
conf
DOI :
10.1109/IAS.2012.6374011
Filename :
6374011
Link To Document :
بازگشت