DocumentCode :
581485
Title :
Cascaded H-Bridge & neutral point clamped hybrid asymmetric multilevel inverter topology for grid interactive transformerless photovoltaic power plant
Author :
Chattopadhyay, Sumit K. ; Chakraborty, Chandan ; Pal, Bikash C.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol. Kharagpur, Kharagpur, India
fYear :
2012
fDate :
25-28 Oct. 2012
Firstpage :
5074
Lastpage :
5079
Abstract :
Hybrid multilevel inverter topology is proposed for high power transformer less grid interactive photovoltaic power plant. Cascaded H-Bridge & Neutral Point Clamp topologies are hybridized to form this topology. Trinary asymmetric ratio of dc bus voltage is adapted for increasing the number of levels. Only three basic switching stages (two single phase H bridge cell and an NPC structure with common source for all phases) are used in each phase to obtain 53 levels in line to line voltage using trinary voltage rato. NPC structure with a common DC bus for all phases is connected to main photovoltaic (PV) array. This is kept at highest voltage to optimize the DC bus capacitor rating, and to reduce dc bus voltage ripple to increase MPPT efficiency. Third harmonic voltage is injected in order to increase the number of voltage levels further, and to increase the DC bus utilization. Increasing the number of voltage levels gives more flexibility to reduce Total Harmonic Distortion (THD) of the system and in turn reduction in cost and size of the power filter. Switching loss is optimized by operating the inverter at fundamental frequency. Nearest voltage level control modulation technique is adapted. The converter is simulated in MATLAB/Simulink. The results are validated through prototype experimentation in the laboratory.
Keywords :
harmonic distortion; invertors; photovoltaic power systems; power filters; MATLAB-Simulink; MPPT efficiency; NPC structure; PV array; THD; cascaded H-bridge topology; dc bus capacitor rating optimization; dc bus voltage ripple reduction; grid interactive transformerless photovoltaic power plant; hybrid asymmetric multilevel inverter; line to line voltage; nearest voltage level control modulation technique; neutral point clamped topology; power filter; single phase H bridge cell; switching loss optimization; third harmonic voltage; total harmonic distortion; trinary asymmetric ratio; trinary voltage rato; turn reduction; Harmonic analysis; Inverters; Laboratories; Probes; Reliability; Switches; Asymmetric hybrid multilevel inverter; MPPT; grid connected photovoltaic system; nearest voltage level control; third harmonic injection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
IECON 2012 - 38th Annual Conference on IEEE Industrial Electronics Society
Conference_Location :
Montreal, QC
ISSN :
1553-572X
Print_ISBN :
978-1-4673-2419-9
Electronic_ISBN :
1553-572X
Type :
conf
DOI :
10.1109/IECON.2012.6389560