DocumentCode :
585341
Title :
Considerations on the line capacitance under surge corona discharge
Author :
Florea, G.A. ; Dragan, G. ; Rodean, I. ; Lipan, Laurentiu Constantin ; Mateescu, E. ; Oltean, M.
Author_Institution :
Power & Lighting Tehnorob S.A., Bucharest, Romania
fYear :
2012
fDate :
17-21 Sept. 2012
Firstpage :
1
Lastpage :
6
Abstract :
To calculate the accurate value of the dynamic capacitance of a line under corona surge is very important taking into account that the dynamic capacitance value is influencing strongly the distortion of the surges travelling on a line toward the substations. So, it is possible to know the most probable shape and amplitude of the surge in any point of the line to allow the designers to take into account the most adequate measures of protection. Also, in the case of the induced overvoltage surges the dynamic capacitance has a major function, the induced overvoltages just in the initiating point being distorted because of the corona discharge and so easier protection measures having to be taken in the medium voltage distribution lines and substations as well.
Keywords :
corona; discharges (electric); overvoltage protection; power overhead lines; substation protection; surge protection; dynamic capacitance value; induced overvoltage surge protection; line capacitance; medium voltage distribution lines; overhead lines; substation protection; surge corona discharge; surge distortion; Capacitance; Conductors; Corona; Discharges (electric); Equations; Surge protection; Surges; amplitude; bundled phases; capacitance; corona discharge; critical voltage; overvoltages; single conductors; voltage surges;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility (EMC EUROPE), 2012 International Symposium on
Conference_Location :
Rome
ISSN :
2325-0356
Print_ISBN :
978-1-4673-0718-5
Type :
conf
DOI :
10.1109/EMCEurope.2012.6396867
Filename :
6396867
Link To Document :