DocumentCode :
587021
Title :
Accuracy comparison of phase- and time-domain methods for PD location in power cable
Author :
Mardiana, Redy ; Firdaus, Ahmad Fajar
Author_Institution :
Department of Electrical Engineering, The Petroleum Institute, Umm Al Nar, Abu Dhabi, UAE
fYear :
2012
fDate :
21-24 Oct. 2012
Firstpage :
1
Lastpage :
4
Abstract :
Accuracy comparison of phase- and time-domain methods for locating partial discharge (PD) in power cables is presented in this paper. The PD location is based on the measurement from two-end of the cable. Phase-domain methods estimate the PD location from the phase difference between the initial waves of a PD signal at the cable terminals. Meanwhile the time-domain methods estimate the PD location from the arrival time interval between the initial waves of a PD signal. To estimate the arrival time, various methods such as peak detection, 50% peak detection, cross correlation, and maximum likelihood are employed. The computer simulation has been carried out using EMTP and the results are presented.
Keywords :
Aluminum; Coils; Copper; Inductance; Pulse width modulation; Cable; Insulation; PD location; Partial discharge;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2012 15th International Conference on
Conference_Location :
Sapporo, Japan
Print_ISBN :
978-1-4673-2327-7
Type :
conf
Filename :
6401787
Link To Document :
بازگشت