Modeling of the dielectric recovery of hot air in insulating nozzles
Author :
Kurz, A. ; Nikolic, P.G. ; Seeger, M. ; Eichhoff, D. ; Schnettler, Armin
Author_Institution :
Inst. for High Voltage Technol., RWTH Aachen Univ., Aachen, Germany
fYear :
2012
fDate :
3-7 June 2012
Firstpage :
374
Lastpage :
377
Abstract :
In standard high voltage gas circuit breakers -important safety elements in today´s power grids-, a small surface layer of polytetrafluoroethylene (PTFE) vaporizes at the high temperatures occurring in the arcing zone during the high current phase of the interruption process. This ablation continues even some hundred microseconds after the arc has been quenched and it actually changes the total gas composition as well as the temperature profile in the arcing zone. Therefore it delays the fast cooling of the arcing zone, which is necessary to prevent dielectric failures. The experimental determination of the dielectric recovery of hot air in insulating nozzles was investigated previously with focus on the substitution of SF6 (sulfur hexafluoride) in circuit breakers for future power grids. The present investigation gives a physical model for the calculation of the previously measured recovery characteristics. CFD-simulations (computational fluid dynamics) are performed for the determination of the relevant physical properties of the decaying quenching gas (density, temperature etc.). These properties serve as input parameters for the developed model. Based on the gas properties resulting from the CFD-simulations it is possible to calculate the effective ionization coefficients and thus the breakdown voltage applying the streamer criterion. Afterwards the calculated breakdown voltages are compared to the measured recovery characteristics. The comparison shows a good agreement between the measurements and the calculation.
Keywords :
SF6 insulation; circuit breakers; computational fluid dynamics; dielectric properties; ionisation; nozzles; power grids; CFD-simulations; PTFE; SF6; arcing zone; breakdown voltage; computational fluid dynamics; decaying quenching gas; dielectric recovery modeling; hot air; insulating nozzles; interruption process; ionization coefficients; physical properties; polytetrafluoroethylene; power grids; safety elements; standard high voltage gas circuit breakers; streamer criterion; surface layer; total gas composition;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Modulator and High Voltage Conference (IPMHVC), 2012 IEEE International
Conference_Location :
San Diego, CA
Print_ISBN :
978-1-4673-1222-6
Type :
conf
DOI :
10.1109/IPMHVC.2012.6518758
Filename :
6518758