DocumentCode
602395
Title
Determination of critical ambience temperature by power transformers loading
Author
Maksimovich, Slobodan M. ; Shiljkut, Vladimir M.
Author_Institution
Electr. Distrib. Co. Elektrodistribucija Beograd, Belgrade, Serbia
fYear
2012
fDate
1-3 Oct. 2012
Firstpage
1
Lastpage
6
Abstract
This paper presents results of the analysis of the rate between permitted maximal peak load of power transformer x/10 kV/kV and its recorded peak load, both as functions of ambience temperature´s average daily value, 8a. Concerning the fact that these functions depend on consumption types, three different consumption areas were analyzed: with electrical, non-electrical and mixed space heating manner. Functions mentioned above were defined according to relevant annual load charts. It has been determined that both functions´ types can be approximated with S-curves or third degree functions. By these functions´ comparison, man can determine critical value of ambience temperature, by which the equivalence of thermally permitted peak load of a power transformer and its consumption area´s peak load demand, guaranties that this power transformer would not be overloaded, by any other ambience temperature.
Keywords
power transformers; space heating; S-curves; consumption area; critical ambience temperature; mixed space heating; permitted maximal peak load; power transformers loading; voltage 10 kV; Ambience; consumption area; coordination; loadability; power transformer; temperature; thermal characteristics;
fLanguage
English
Publisher
iet
Conference_Titel
Power Generation, Transmission, Distribution and Energy Conversion (MEDPOWER 2012), 8th Mediterranean Conference on
Conference_Location
Cagliari
Electronic_ISBN
978-1-84919-715-1
Type
conf
DOI
10.1049/cp.2012.2019
Filename
6521861